top of page

Shortfalls of the Category Method Instead of Incident Energy Calculations to Determine Arc Flash PPE

  • Writer: Jeff Kershner
    Jeff Kershner
  • May 12
  • 3 min read

One of the biggest misunderstandings we see regarding arc flash protection is the improper association people make between the PPE “categories” listed on the NFPA tables and incident energy values. It's important to understand that you should not correlate PPE category levels directly with calculated incident energy values. Let's break down why.

A Simple Example


Using NFPA 70E 2024, consider the following example:

  • Equipment constraints:


    • Maximum available fault current: 25 kA

    • Maximum fault clearing time: 0.03 sec (2 cycles)

    • Minimum working distance: 18 inches

According to the NFPA 70E PPE Category Table, under these parameters, you would be required to wear Arc Flash PPE Category 2, which mandates a minimum arc rating of 8 cal/cm².


table showing arc flash PPE categories

However, if you model these exact parameters (25kA and 0.03s clearing time) using engineering software, the calculated incident energy comes out to approximately 1.6 cal/cm².  


table showing arc rated clothing PPE categories

This calculated result is just barely above the minimum threshold where arc flash protection is required at an 18" working distance.


Disclaimer: The example calculation above is for illustrative purposes only. It is not representative of all equipment and should not be used to justify reducing PPE based on this example alone.



What Does This Tell Us?


  • The tables in NFPA 70E are designed to protect you conservatively when you cannot perform a full arc flash analysis.


  • The "category level" of your clothing is only meant to ensure appropriateness for the hazard under the table’s assumptions — it does not reflect the actual incident energy you might encounter.


Simply put, Category 2 clothing does not mean you are facing an 8 cal/cm² hazard. It means you need clothing rated for at least 8 cal/cm² under the assumed table conditions.


Another Important Comparison


Suppose you use the table method correctly and determine that Category 1 is necessary. This category requires:

  • PPE with a minimum arc rating of 4 cal/cm²

  • No balaclava required

Making an inappropriate assumption that Category 1 PPE will protect you up to 4 cal/cm2 could be very dangerous.  If you are actually working on equipment with a calculated incident energy of 4 cal/cm², you are required to wear a balaclava ("where the back of the head is inside the arc flash boundary").

This highlights again: Category assignment and actual incident energy requirements are not the same thing.


Important Notes About Using the Table Method


You may only use Table 130.7(C)(15)(a) Arc Flash PPE Categories for AC Systems if all of the following are verified:


  • Available fault current does not exceed 25kA

  • Fault clearing time does not exceed 0.03 seconds (2 cycles)

  • Minimum working distance is 18 inches (455 mm)

If you cannot verify these parameters, you cannot rely on the table method.

And realistically, without performing an arc flash analysis, it is very difficult to know the available fault current and clearing time. Many standard fuses and breakers will not clear within the time requirements at the available fault current.

A 2022 IEEE study concluded:

"Even if the worker can properly identify these values, it is quite possible that an arc flash event will result in much higher incident energy than expected because Iarc is much lower than Ibf and the protection is much slower at that Iarc." [Valdes, Sullivan, Halle (2022), ANALYSIS OF NFPA 70E TABLE 130(C)(15)(a) USING IEEE 1584-2018 CONSTANT ENERGY BOUNDARIES, ESW 2022-06]


Why a Full Arc Flash Analysis Matters


Without a proper arc flash analysis, you run serious risks:

  • Wearing insufficient PPE without realizing it

  • Overdressing unnecessarily, which can impair mobility and productivity

  • Assuming your hazard is lower or higher than it actually is, leading to unsafe work practices

In fact, in most cases, a full evaluation will show that less PPE is needed than when using the Category method alone, meaning safer, more practical, and more cost-effective protection.

Electrical safety is complicated. If you’re unsure whether the table method applies to your facility, or if you want a more accurate assessment, contact one of Guidant’s experienced engineers. We’re here to help you protect your workers and make sure you’re compliant and confident in your electrical safety program.


bottom of page